Cable Glands Hawke 501/453/RAC
Hazardous Area
Flameproof Exd & Increased Safety Exe
Dual Certifi ed ATEX / IECEx
Application
• Outdoor or indoor use.
• For use with single wire armour ‘W’, wire braid ‘X’, steel tape armour ‘Z’,
elastomer and plastic insulated cables.
• See technical section for installation rules and regulations.
Technical Data
• Flameproof Exd and Increased Safety Exe II 2 GD ExtD A21.
• Certifi cate No’s: Baseefa06ATEX0056X and IECEx BAS 06.0013X.
• Suitable for use in Zone 1, Zone 2, Zone 21, Zone 22 and in
Gas Groups IIA, IIB and IIC.
• Construction and Test Standards: IEC/EN 60079-0, IEC/EN 60079-1,
IEC/EN 60079-7, IEC/EN 61241-0 and IEC/EN 61241-1.
• Ingress Protection: IP66, IP67 and IP 68 (30 metres for 7 days)
to IEC/EN 60529 and NEMA 4X.
• Deluge Protection to DTS01 (Deluge Seal Optional).
• Operating Temperature Range: -60°C to +80°C.
• Assembly Instruction Sheet: AI 302.